Chapter 4 Installation and Wiring
4-9
(4) Use a flat-blade screwdriver to tighten the appropriate terminal screws on the terminal connec-
tor from step 3.
Use a flat-blade screwdriver (Size 0.4 x 2.5) to tighten the terminal screws.
The torque required to tighten these screws is 0.28Nm
(2.5 [Lb
in])
.
The power connector cannot be removed because it is mounted to GP unit. Do not
attempt to remove or tamper with the power connector. It may damage the power
connector.
Be sure to loosen the terminal screws before pulling out the power cord. The power
connector may be damaged by pulling the power cord when attached to the power
connector.
Do not solder the cable connection. Doing so may damage the unit due to abnormal
heat or cause a fire.
Be sure to twist the power cords together, up to the power connector.